Insulation Resistance |
| Test Voltage |
250V/500V/1000V |
| Measuring Range (Mid-scale Value) |
100MΩ/200MΩ/400MΩ
(1MΩ) (2MΩ) (4MΩ) |
Output Voltage
on open circuit |
Rated test voltage+20%, -0% |
| Nominal Current |
1mA DC min. |
Output Short
Circuit Current |
1.3 mA DC approx. |
| Accuracy |
0.1~10MΩ/0.2~20MΩ/0.4~40MΩ
(Accuracy Guaranteed Ranges)
±5% of indicated value |
|
Continuity |
Measuring Ranges
(Mid-scale Value) |
2Ω/20Ω
(1Ω)(10Ω) |
Output Voltage
on open circuit |
4~9V DC |
| Measuring Current |
200mA DC min. |
| Accuracy |
|±3% of scale length |
|
General |
| Safety Standard |
IEC61010-1 CAT.III 300V Pollution
Degree 2
IEC61010-2-031
IEC61557-1/2/4 |
| IP Rating |
IEC60529-IP54 |
| EMC Standard |
IEC61326-1 |
| Withstand Voltage |
3700V AC for 1 minute |
| Power Source |
R6P(AA)(1.5V) × 6 |
| Dimensions |
185(L) × 167(W) × 89(D)mm |
| Weight |
860g approx. |
| Accessories |
7122(Test leads) Pouch for test leads
8923(F500mA/600V fuse) × 2
R6P(AA) × 6
Shoulder Strap
Instruction Manual |